| Model Name | PEA-RP200WJA | ||
|---|---|---|---|
| Type | Inverter | ||
| Indoor Unit | PEA-RP200WJA | ||
| Outdoor Unit | PUHZ-RP200YK2A | ||
| Refrigerant | R410A | ||
| Cooling | |||
| Capacity (Rated Conditions) | kW | 18.9 | |
| Capacity (Min – Max) | kW | 9 – 22.4 | |
| Air Flow (Low – Hi) | l/s | 833-1017-1200 | |
| External Static Pressure | Pa | 60-75-100-150 | |
| AEER/EER (Rated Conditions) *2 | 3.11/3.19 | ||
| AEER [Part load %]*1 | 3.75 | ||
| Sound Pressure Levels *3 | |||
| Indoor at 1.5m (Low – Hi) | dBA | 38-41-44 | |
| Outdoor at 1m (Quiet Mode) | dBA | 58 | |
| Heating | |||
| Capacity (Rated Conditions) | kW | 22.4 | |
| Capacity (Min – Max) | kW | 9.5 – 25 | |
| Air Flow (Low – Hi) | l/s | 833-1017-1200 | |
| ACOP/COP (Rated Conditions) *2 | 3.18/3.25 | ||
| Sound Pressure Levels *3 | |||
| Indoor at 1.5m (Low – Hi) | dBA | 38-41-44 | |
| Outdoor at 1m | dBA | 59 | |
| Dimensions | |||
| Indoor (HxWxD) | mm | 470x1370x1120 | |
| Outdoor (HxWxD) | mm | 1338x1050x330+30 | |
| Weight | |||
| Indoor | kg | 108 | |
| Outdoor | kg | 135 | |
| Electrical Supply | |||
| Three Phase | 415 volt / Three Phase / 50 Hertz | ||
| Breaker Size | |||
| Three Phase | A | 32 | |
| Piping | |||
| maximum length | m | 75 | |
| maximum height | m | 30 | |
| Guaranteed Operating Range | |||
| – Cooling*4 | °C | -5 (-15) ~ 52 | |
| – Heating | °C | ||
*1 MEPS compliant part load
*2 Rated EER/COP for PEA-RP170/200WJA are measured at ESP 75 Pa.
*3 Sound pressure level for PEA-RP170/200WJA are measured in anechoic chamber at ESP 150 Pa.
*4 With optional air protection guide, the operation at -15°C outdoor temperature is possible.